← Back to map

Moselle

Jones County, Mississippi · EIA plant ID 2070 · Operator: South Mississippi El Pwr Assn
Natural gasNatural Gas Fired Combined CycleNatural Gas Fired Combustion TurbineNatural Gas Steam TurbineMISOBA: MISO
Nameplate511MWSummer 477 MW
Generators7in service
Net generation1,577GWh12 mo to Aug 2026
Capacity factor38%gas/coal/oil units, summer MW
Heat rate8,908Btu/kWhfossil units, electric fuel, HHV
First online1970Runs as baseload

The 12-month figures include preliminary EIA-923 months, which EIA revises. Final data runs through Dec 2025.

Monthly net generation

EIA-923, all units at the plant. Net of station use; storage can go negative.
FinalPreliminary
050100150200GWh2001200320052007200920112013201520172019202120232025

Capacity factor by year

Net MWh ÷ (summer MW × hours), gas/coal/oil units. Each year uses that year's EIA-860 ratings; the hollow dot is the latest 12 months.
0%20%40%2005201020152020202537.7% · 12 mo

Heat rate by year

Electric fuel MMBtu × 1000 ÷ net MWh (Btu/kWh, HHV), fossil units only; CT + CA counted as one combined-cycle block.
6,0008,00010,00012,000200520102015202020258,908 Btu/kWh · 12 mo
Annual data table
YearNet GWhCapacity factorHeat rate (Btu/kWh)
2001399.8——
2002474.7——
2003401.917.6%12,111
2004394.717.8%12,563
200531014.0%12,448
2006342.413.2%12,435
2007267.59.3%12,455
2008123.74.3%12,846
20092077.2%12,495
20102649.2%12,373
2011272.49.5%12,185
2012782.722.9%8,890
201395122.8%8,392
2014888.521.3%8,610
20151,532.636.7%8,483
20161,54136.8%8,529
2017912.421.8%8,864
2018968.523.2%9,210
20191,23429.5%8,601
20201,643.239.2%8,520
20211,314.531.5%8,661
20221,222.529.3%8,897
20232,141.851.3%8,892
20242,009.348.0%8,985
20251,659.339.7%8,842

Fuel capability

Gas-fired turbines (CT/GT/CA/CS) that can also burn liquid fuel. EIA-860 Schedule 3 for capability, EIA-923 for actual burn.
StatusListed in EIA-860, no liquid burn in 36 months
Liquid fuel burned · 36 mo0 MMBtu
Last month with liquid burn—
Switch while operatingYes
Net summer MW on gas75
Net summer MW on oil75
Time gas → oilup to 6 h (EIA 6H)
Time oil → gasup to 6 h (EIA 6H)

Generators

EIA-860 (annual) with EIA-860M updates through Sep 2026. EIA-923 reports generation by plant, prime mover and fuel, not by unit, so unit-level output isn't shown.
Gen IDTechnologyPrime moverNameplate MWSummer MWOnlineStatusPlanned retirementOEM / model
1Natural Gas Fired Combined CycleCA5959Aug 1970Operating—coming soon
2Natural Gas Fired Combined CycleCA5959Aug 1970Operating—coming soon
3Natural Gas Steam TurbineST5959Aug 1970Operating—coming soon
4Natural Gas Fired Combustion TurbineGT8375Jun 1997Operating—coming soon
5Natural Gas Fired Combustion TurbineGT83.575Jun 2006Operating—coming soon
GTG1Natural Gas Fired Combined CycleCT83.575May 2012Operating—coming soon
GTG2Natural Gas Fired Combined CycleCT83.575Nov 2012Operating—coming soon

Owner / operator

Operator: South Mississippi El Pwr Assn. Ownership shares by in-service nameplate MW (EIA-860 Schedule 4; units not listed there are wholly owned by the operator).
South Mississippi El Pwr Assn100.0%511 MW

Nearby plants

Within 80 km.
OE_MS4—20 km
Sumrall II Solar Farm52 MW22.8 km
Sumrall I Solar Farm52 MW23.3 km
Hattiesburg Solar Farm50 MW28 km
R D Morrow558 MW35.5 km
Georgia-Pacific Taylorsville Plywood7 MW37.7 km