← Back to map

Exira

Audubon County, Iowa · EIA plant ID 56013 · Operator: Western Minnesota Mun Pwr Agny
Natural gasNatural Gas Fired Combustion Turbine⛽ Dual-fuelMISOBA: SWPP
Nameplate182MWSummer 140 MW
Generators3in service
Net generation243GWh12 mo to Dec 2025
Capacity factor20%gas/coal/oil units, summer MW
Heat rate10,685Btu/kWhfossil units, electric fuel, HHV
First online2004Runs as intermediate

Monthly net generation

EIA-923, all units at the plant. Net of station use; storage can go negative.
FinalPreliminary
010203040GWh20052007200920112013201520172019202120232025

Capacity factor by year

Net MWh ÷ (summer MW × hours), gas/coal/oil units. Each year uses that year's EIA-860 ratings; the hollow dot is the latest 12 months.
0%10%20%2005201020152020202519.8% · 12 mo

Heat rate by year

Electric fuel MMBtu × 1000 ÷ net MWh (Btu/kWh, HHV), fossil units only; CT + CA counted as one combined-cycle block.
8,0009,00010,00011,0002005201020152020202510,685 Btu/kWh · 12 mo
Annual data table
YearNet GWhCapacity factorHeat rate (Btu/kWh)
200528.93.3%9,625
200634.14.2%9,977
200769.36.1%9,598
200820.51.7%9,118
20094.10.3%9,900
20103.70.3%10,051
201111.50.9%10,053
201245.43.7%9,886
201310.10.8%9,674
20145.10.4%10,020
201520.81.7%—
201639.83.3%—
201746.13.8%—
201884.36.9%10,358
2019103.98.5%11,046
2020806.5%10,706
2021123.410.1%10,566
2022156.912.8%10,361
2023229.818.7%10,663
2024313.725.5%10,401
2025243.519.8%10,685

Fuel capability

Gas-fired turbines (CT/GT/CA/CS) that can also burn liquid fuel. EIA-860 Schedule 3 for capability, EIA-923 for actual burn.
StatusLikely still dual fuel
Liquid fuel burned · 36 mo64,961 MMBtu
Last month with liquid burnDec 2025
Switch while operatingYes
Net summer MW on gas139
Net summer MW on oil139
Time gas → oilup to 1 h (EIA 1H)
Time oil → gasup to 1 h (EIA 1H)

Generators

EIA-860 (annual) with EIA-860M updates through Sep 2026. EIA-923 reports generation by plant, prime mover and fuel, not by unit, so unit-level output isn't shown.
Gen IDTechnologyPrime moverNameplate MWSummer MWOnlineStatusPlanned retirementOEM / model
U1Natural Gas Fired Combustion TurbineGT60.546.7Apr 2004Operating—coming soon
U2Natural Gas Fired Combustion TurbineGT60.546.7May 2004Operating—coming soon
U3Natural Gas Fired Combustion TurbineGT60.546.7Apr 2007Operating—coming soon

Owner / operator

Operator: Western Minnesota Mun Pwr Agny. Ownership shares by in-service nameplate MW (EIA-860 Schedule 4; units not listed there are wholly owned by the operator).
Western Minnesota Mun Pwr Agny100.0%182 MW

Nearby plants

Within 80 km.
Atlantic10 MW13.5 km
Wiota2 MW14.1 km
Anita3 MW15 km
Eclipse Wind Farm207 MW20 km
Green Energy Machine2 MW20.9 km
Roseman2 MW21.1 km