← Back to map

Marshall (MO)

Saline County, Missouri · EIA plant ID 2144 · Operator: City of Marshall - (MO)
Natural gasNatural Gas Fired Combustion TurbineNatural Gas Internal Combustion EnginePetroleum Liquids⛽ Dual-fuelSPPBA: SWPP
Nameplate31MWSummer 29 MW
Generators6in service
Net generation1GWh12 mo to Dec 2025
Capacity factor1%gas/coal/oil units, summer MW
Heat rate12,858Btu/kWhfossil units, electric fuel, HHV
First online1972Runs as rarely runs

Monthly net generation

EIA-923, all units at the plant. Net of station use; storage can go negative.
FinalPreliminary
-5051015GWh2001200320052007200920112013201520172019202120232025

Capacity factor by year

Net MWh ÷ (summer MW × hours), gas/coal/oil units. Each year uses that year's EIA-860 ratings; the hollow dot is the latest 12 months.
0%10%20%200520102015202020250.5% · 12 mo

Heat rate by year

Electric fuel MMBtu × 1000 ÷ net MWh (Btu/kWh, HHV), fossil units only; CT + CA counted as one combined-cycle block.
8,00010,00012,00014,00016,0002005201020152020202512,858 Btu/kWh · 12 mo
Annual data table
YearNet GWhCapacity factorHeat rate (Btu/kWh)
200137.2——
200243.5——
200335.37.3%16,020
200428.95.9%14,299
200548.410.1%14,264
200680.916.8%14,035
200797.820.3%13,605
200895.919.9%13,494
200943.79.1%13,287
201027.75.7%13,577
201122.74.7%13,971
20121.90.4%12,558
20136.31.3%13,475
20140.20.0%14,888
20154.60.9%13,602
20160.30.1%17,024
20170.20.1%13,097
20180.70.3%14,712
20196.42.5%15,703
20202.30.9%15,542
20219.93.9%15,289
20227.32.9%15,050
20231.70.7%12,102
20240.40.2%10,597
20251.30.5%12,858

Fuel capability

Gas-fired turbines (CT/GT/CA/CS) that can also burn liquid fuel. EIA-860 Schedule 3 for capability, EIA-923 for actual burn.
StatusLikely still dual fuel
Liquid fuel burned · 36 mo34 MMBtu
Last month with liquid burnDec 2025
Switch while operatingYes
Net summer MW on gas14
Net summer MW on oil14
Time gas → oilup to 1 h (EIA 1H)
Time oil → gasup to 1 h (EIA 1H)

Generators

EIA-860 (annual) with EIA-860M updates through Sep 2026. EIA-923 reports generation by plant, prime mover and fuel, not by unit, so unit-level output isn't shown.
Gen IDTechnologyPrime moverNameplate MWSummer MWOnlineStatusPlanned retirementOEM / model
10Natural Gas Internal Combustion EngineIC6.36.3Jun 1990Operating—coming soon
11Natural Gas Internal Combustion EngineIC6.36.3Jan 1994Operating—coming soon
7Petroleum LiquidsIC10.9Jun 1988Operating—coming soon
8Petroleum LiquidsIC10.9Jun 1988Operating—coming soon
9Petroleum LiquidsIC10.9Jun 1988Operating—coming soon
GT1Natural Gas Fired Combustion TurbineGT15.214May 1972Operating—coming soon
3Natural Gas Steam TurbineST43.9Jun 1948Retired Jul 2014—coming soon
4Conventional Steam CoalST65.8Jul 1956Retired Jul 2016—coming soon
5Conventional Steam CoalST16.516Jul 1967Retired Dec 2016—coming soon

Owner / operator

Operator: City of Marshall - (MO). Ownership shares by in-service nameplate MW (EIA-860 Schedule 4; units not listed there are wholly owned by the operator).
City of Marshall - (MO)100.0%31 MW

Nearby plants

Within 80 km.
Marshall Energy Center—0.1 km
Marshall Solar Farm (MO)3 MW3.1 km
Carrollton21 MW36 km
Higginsville52 MW44.2 km
Fayette11 MW45.4 km
Higginsville Solar Farm3 MW46.9 km